KNX PS640-IP Router / Power Supply System

Bus Voltage and 24 V DC | Ethernet Interface (LAN)
KNX bus voltageFor 24 V DCEthernet Interface

The Power Supply System KNX PS640-IP combines the central functions of a KNX bus line: Power supply with throttle, IP router and IP interface:
The Power Supply Unit of the KNX PS640-IP delivers a 29 V bus voltage for the KNX system and 24 V DC supply voltage for 24 V devices.
Special operating conditions such as short circuit, electrical surge, overcharge or excess temperature are recorded and may be read off on the display. The present power discharge is displayed as well. It is possible to reset the connected bus devices directly by means of the key pad.

The IP router of the KNX PS640-IP allows for forwarding of telegrams between different lines via a rapid LAN (IP) backbone. The KNX PS640-IP therfore also takes on the function of a line coupler.

In parallel, the KNX PS640-IP can be used as interface for accessing the bus access via IP. Like this, the KNX system can be configuered and supervised from any PC in the LAN (Tunnelling).

Click on the image to enlargen the picture

Functions and Operation:

  • Delivers a 29 V KNX bus voltage (reduced), output current max. 640 mA, short-circuit proof
  • Delivers 24 V DC (not reduced), output current max. 150 mA
  • Reset of a line directly on the device
  • Record of operating hours, overload, external overvoltage, internal overvoltage, short circuit and excess temperature
  • Display of operating data bus voltage, bus current and temperature of the device
  • The display may be shown in German, English, Spanish or Dutch 
  • Routing: Transfer of KNX data via LAN (rapid backbone)
  • Line coupler function via LAN
  • Tunnelling: Configuration and supervising of the KNX system from any PC in the LAN

Technical Data:

HousingPlastic material
ColourWhite
MountingSnap-on fitting on mounting rails
Protection categoryIP 20
Dimensionsapprox. 123 x 89 x 61 (W x H x D, mm), 7 width units
Weight approx. 395 g
Ambient temperatureOperation -5…+45 °C, storage -25…+70°C
Ambient air humiditymax. 95% RH, avoid bedewing
Operating voltage230 V AC , 50 Hz
Power consumptionFull load: approx. 28 W
Standby: approx. 2.3 W
Outputs• KNX bus voltage 29 Volt (reduced),
 Output current max. 640 mA, short-circuit proof
• 24 V DC (not reduced), Output current max. 150 mA
• LAN connector RJ45; 10BaseT (10Mbit/s), Supported
 internet protocols: ARP, ICMP, IGMP, UDP/IP and DHCP

Scope of Delivery:

  • Rail-mounted device with display and keypad
  • Data sheet with installation instruction and description of parameter setting (German or English)
  • Product file VD2 (German, English, French, Italian) as download

Contact