KNX S-B2-UP Actuator
![]() | ![]() | ![]() | ![]() |
The Actuator KNX S-B2-UP controls shadings (blinds, awnings, roller shutters) or windows. The automatic for this may be provided externally or internally. An internal automatic offers numerous options for blocking, locking (e. g. master–slave) and priority settings (e. g. manual–automatic). Scenes may be stored and recalled via the bus.
Two binary inputs may be used for direct operation (e. g. manual push-buttons) or as bus inputs.
![]() KNX S-B2-UP 230 V AC for a 230 V AC motor | ![]() KNX S-B2-UP 24 V DC for a 24 V DC motor |
Functions and Operation:
- For drive mechanism of shading or window
- 2 binary inputs
- 8 channel scene control for operating position (for blinds also slat position)
- Slat tracking for blinds according to the position of the sun
- Position memory (operating position) with a 1 bit object (Storage and recall e. g. with push-button)
- Position feedback (operating position, for blinds also slat position)
- Control by internal or external automatic
- Setting of the priority of manual or automatic control by time or via communication object
- Mutual locking of two drives by means of zero position sensors avoids collisions e. g. of shading and window (master–slave)
- Blocking objects and alarm messages have different priority so that safety functions always are higher-ranking (e. g. wind blocking)
- Configuration is accomplished by means of the KNX software ETS
Technical Data:
| Housing | Plastic material |
| Colour | White |
| Mounting | In-wall (in socket Ø 60 mm, 60 mm deep) |
| Protection category | IP 20 |
| Dimensions | approx. 50 x 51 x 41 (W x H x T, mm) |
| Weight | 230 V version: approx. 90 g 24 V version: approx. 70 g |
| Ambient temperature | Operation -20…+70°C, storage -30…+85°C |
| Ambient air humidity | 5…80% RH, avoid bedewing |
| Operating voltage | Available for 230 V AC or for 24 V DC |
| Current | At the bus: 10 mA At 24 V DC: 40 mA At 230 V AC: 2 mA AC |
| Output | 1 x Drive mechanism 230 V version: max. 500 W, fused with microfuse T6.3 A 24 V version: max. 50 W |
| Inputs | 2 x Binary input (for potential-free contacts) |
| Data output | KNX +/- bus terminal plug |
| Communication objects | 88 |
Scope of Delivery:
- Actuator with housing
- Data sheet with installation instruction (German or English)
- Product file VD2 (German, English, Spanish) as download
- Socket Ø 60 mm, 60 mm deep
Accessories:
- Manual with description of parameter setting (German, English) as download. Printed version can be ordered with costs