KNX S-B2-UP Actuator

AwningBlindRoller ShutterWindow

The Actuator KNX S-B2-UP controls shadings (blinds, awnings, roller shutters) or windows. The automatic for this may be provided externally or internally. An internal automatic offers numerous options for blocking, locking (e. g. master–slave) and priority settings (e. g. manual–automatic). Scenes may be stored and recalled via the bus.

Two binary inputs may be used for direct operation (e. g. manual push-buttons) or as bus inputs.


KNX S-B2-UP 230 V AC
for a 230 V AC motor

KNX S-B2-UP 24 V DC
for a 24 V DC motor

Functions and Operation:

  • For drive mechanism of shading or window
  • 2 binary inputs
  • 8 channel scene control for operating position (for blinds also slat position)
  • Slat tracking for blinds according to the position of the sun
  • Position memory (operating position) with a 1 bit object (Storage and recall e. g. with push-button)
  • Position feedback (operating position, for blinds also slat position)
  • Control by internal or external automatic
  • Setting of the priority of manual or automatic control by time or via communication object
  • Mutual locking of two drives by means of zero position sensors avoids collisions e. g. of shading and window (master–slave)
  • Blocking objects and alarm messages have different priority so that safety functions always are higher-ranking (e. g. wind blocking)
  • Configuration is accomplished by means of the KNX software ETS

Technical Data:

HousingPlastic material
ColourWhite
MountingIn-wall (in socket Ø 60 mm, 60 mm deep)
Protection categoryIP 20
Dimensionsapprox. 50 x 51 x 41 (W x H x T, mm)
Weight230 V version: approx. 90 g
24 V version: approx. 70 g
Ambient temperatureOperation -20…+70°C, storage -30…+85°C
Ambient air humidity5…80% RH, avoid bedewing
Operating voltageAvailable for 230 V AC or for 24 V DC
CurrentAt the bus: 10 mA
At 24 V DC: 40 mA
At 230 V AC: 2 mA AC
Output1 x Drive mechanism
230 V version: max. 500 W, fused with microfuse T6.3 A
24 V version: max. 50 W
Inputs2 x Binary input (for potential-free contacts)
Data outputKNX +/- bus terminal plug
Communication objects88

Scope of Delivery:

  • Actuator with housing
  • Data sheet with installation instruction (German or English)
  • Product file VD2 (German, English, Spanish) as download
You will need in addition (not supplied):
  • Socket Ø 60 mm, 60 mm deep

Accessories:

  • Manual with description of parameter setting (German, English) as download. Printed version can be ordered with costs

Contact

Please call us
+49 (0) 70 56 / 93 97-0
Please contact us
Subscribe newsletter
Rate us
Recommend page

Downloads

News

Monitoring the fill level of tanks

10.05.2013 12:56

Ultrasonic Sensor and Evaluation Unit KNX SO250 basic